Primary-Network Heating Station for a 2-Million-m² District Heating Zone in Northeast China

Urban district heating in northern China generally uses a four-tier system of "combined heat and power plant → primary network → heating station → secondary network → end users." The primary network runs at water temperatures up to 130 ℃, while the secondary network only reaches 85 ℃; in between, heating stations are required for energy transfer and pressure isolation. This project designed and built four parallel large plate heat exchanger units in one pass for the 2-million-m² heating area of a new district in a Northeast China city.

1. Project Background

Customer

Thermal utility company of a new district in a Northeast China city, responsible for heating operations for 2 million m² of commercial and residential space in the district.

Heat Source

Upstream combined heat and power (CHP) plant, primary network design temperature 130/70 ℃, pressure rating PN25.

Design Parameters

  • Total heating area: 2 million m²
  • Design heat index: 45 W/m²
  • Total heat load: 90 MW
  • Divided into 4 stations, 25 MW per station

2. Technical Solution

Uses SAMIT BR1.0 large plate heat exchangers with a heat transfer area of 240 m² per unit, configured as 1 duty + 1 standby per station (mutual standby). The primary side (130/70 ℃) and secondary side (85/60 ℃) are completely isolated by the plate heat exchanger, preventing primary-network high pressure from directly entering the residential end-loop piping.

ParameterPrimary side (high-temperature side)Secondary side (low-temperature side)
MediumPower plant demineralized waterSoftened circulating water
Inlet/Outlet temperature130 / 70 ℃60 / 85 ℃
Flow rate860 m³/h1550 m³/h
Pressure ratingPN25PN16
Pressure drop52 kPa48 kPa
Heat duty25 MW (per unit)

3. Process Flow

District Heating Primary-Network Heating Station Flow CHP Plant 130 ℃ hot water PN25 Primary supply 130 ℃ SAMIT BR1.0 240 m² PHE Heat duty 25 MW 1 duty + 1 standby Primary return 70 ℃ Secondary supply 85 ℃ End-User Heating Radiators / Underfloor 2 million m² Secondary return 60 ℃ Secondary Make-up / Pressurization Deaeration + Softening + VFD make-up pump 25 MW per unit · 4 stations in parallel = 100 MW · Primary/secondary pressure fully isolated

4. Implementation Process

  • Design: Back-calculated the heat index from the local outdoor design temperature of -19 ℃; sized each station at 25 MW and distributed the 4 stations close to loads to reduce network losses
  • Equipment supply: 8 SAMIT BR1.0 plate heat exchangers (2 per station, 1 duty + 1 standby), paired with VFD circulating pumps, pressurization make-up units, and automation cabinets
  • Commissioning: During the extreme cold period at -22 ℃, the measured return temperature was stable; the end-of-secondary-network temperature difference was only ±1.5 ℃; main plant room noise ≤ 75 dB(A)

Design highlights: The primary-network pressure PN25 and secondary-network PN16 are fully isolated by the plate heat exchanger, so even if the secondary-network end loops introduce impurities during renovation, there is no backflow contamination of the primary network (CHP plant side). At the same time, the high K value of the plate heat exchanger (5500 W/(m²·K)) means it requires only 1/4 the footprint of a shell-and-tube unit for the same heat duty.

5. Operating Results

Heat Exchange Capacity

Each station operated stably at the full 25 MW load, with the K value maintained at 5500 W/(m²·K).

Footprint

Saves 75% of footprint compared with a traditional shell-and-tube scheme; each station's plant room is only 80 m².

O&M Cost

Zero failures over 3 heating seasons; annual O&M cost down 40% versus shell-and-tube.

6. Lessons Learned

The key to selecting large district heating stations is "high temperature difference + large temperature drop." A primary-network temperature difference of 60 ℃ (130/70 ℃) plus a secondary-network difference of 25 ℃ (85/60 ℃) lets SAMIT plate heat exchangers transfer the maximum heat in the smallest footprint. For projects above 2 million m², we recommend a multi-station parallel + plate heat exchanger unit layout to avoid the O&M risk of a single oversized station.